Date _______________
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
SET.11 of 35
SEL-387-0, -5, -6 Relay Settings Sheets
Group Settings (SET Command)
Phase Inv.-Time O/C Time-Dial (US 0.5–15.0, IEC 0.05–1.00)
51P4TD
=
Phase Inv.-Time O/C EM Reset (Y, N)
51P4RS
=
51P4 Torque Control (SEL
OGIC
control equation)
51P4TC
=
Winding 4 Negative-Sequence O/C Elements
NOTE:
All negative-sequence element pickup settings are in terms of 3I
2
.
Neg.-Seq. Def.-Time O/C Level 1 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50Q41P
=
Neg.-Seq. Level 1 O/C Delay (0.5–16000.0 cycles)
50Q41D
=
50Q41 Torque Control SEL
OGIC
control equation)
50Q41TC
=
Neg.-Seq. Inst. O/C Level 2 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50Q42P
=
50Q42 Torque Control (SEL
OGIC
control equation)
50Q42TC
=
Neg.-Seq. Inv.-Time O/C PU
(OFF, 0.5–16.0 A secondary) (5 A)
(OFF, 0.1–3.2 A secondary) (1 A)
51Q4P
=
Neg.-Seq. Inv.-Time O/C Curve (U1–U5, C1–C5)
51Q4C
=
Neg.-Seq. Inv.-Time O/C Time-Dial
(US 0.5–15.0, IEC 0.05–1.00)
51Q4TD
=
Neg.-Seq. Inv.-Time O/C EM Reset (Y, N)
51Q4RS
=
51Q4 Torque Control SEL
OGIC
control equation)
51Q4TC
=
Winding 4 Residual O/C Elements
Residual Def.-Time O/C Level 1 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50N41P
=
Residual Level 1 O/C Delay (0–16000 cycles)
50N41D
=
50N41 Torque Control (SEL
OGIC
control equation)
50N41TC
=
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...