3.9
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Differential, Restricted Earth Fault, Thermal, and Overcurrent Elements
Differential Element
Figure 3.9
DC Blocking (DCBL1) Logic (All But SEL-387-0)
Setting Descriptions
Differential Element Enable (E87W1—E87W4)
Range: Y, N, Y1
The SEL-387 has four sets of three-phase current inputs. Depending on the
application, you may not need all of these inputs for the differential zone of
protection. You can configure any unused terminals for stand-alone
overcurrent protection. The E87W
n
setting specifies which of the terminals
the relay is to include in the differential calculation. An independent setting,
EOC
n
, exists to enable the overcurrent and demand metering elements.
Selecting Y for E87W
n
enables differential element settings for the
corresponding winding. Selecting N for E87W
n
disables differential element
settings for the corresponding winding; the relay hides the settings, and they
are unavailable for use.
For all relays but the SEL-387-0, selecting Y1 makes the fourth-harmonic
(PCT4), dc ratio blocking (DCRB), and harmonic restraint (HRSTR) settings
available on all enabled (Y or Y1) windings. This is the only difference
between Y and Y1 selection.
CT Connection (W1CT—W4CT)
Range: D, Y
To perform calculations for TAP
n
values, the relay uses information on
whether the CTs are connected in delta (D) or wye (Y) for each winding. If the
CTs are connected in delta, the relay raises the TAP
n
value by a factor of
1.732.
Also, if the CTs on a particular winding “
n
” are connected in delta
(W
n
CT = D), then the secondary currents into the corresponding SEL-387
current inputs (IAW
n
, IBW
n
, and ICW
n
) are modified before being displayed
or used in:
➤
breaker monitoring (
BRE
command)
➤
instantaneous metering (
METER
command)
➤
demand metering (
METER D
and
METER P
commands)
➤
through-fault event monitoring (
TFE
command)
For delta-connected CTs, the secondary currents into the SEL-387 current
inputs are phase-phase difference currents (e.g., phase-phase difference
current I
A
–I
B
flows into current input IAW
n
). To create a pseudo phase-
neutral value for display or use in algorithms, these phase-phase difference
currents are divided by
3 (divided by 1.732).
DCBL1
Min
Max
_
+
0.1
DCR
S+
S-
Differential Current
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...