B.5
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
SEL-300 Series Relays Firmware Upgrade Instructions
Upgrade Procedure
Figure B.5
Terminal Emulation Startup Prompt
Failure to Connect
If you do not see the Access Level 0
=
prompt, press
<Enter>
again. If you
still do not see the Access Level 0
=
prompt, you have either selected the
incorrect serial communications port on the computer, or the computer speed
setting does not match the data transmission rate of the relay. Perform the
following steps to reattempt a connection:
Step 9. From the
Call
menu, choose
Disconnect
to terminate
communication.
Step 10. Correct the port setting:
a. From the
File
menu, choose
Properties
.
You should see a dialog box similar to
.
b. Select a different port in the
Connect using:
list box.
Figure B.6
Correcting the Port Setting
Step 11. Correct the communications parameters:
a. From the filename
Properties
dialog box shown in
Configure
.
You will see a dialog box similar to
.