10.10
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Testing and Troubleshooting
Acceptance Testing
Figure 10.4
Test Connections for Balanced Load With Two-Phase
Current Sources
Winding Overcurrent
Each winding overcurrent element that is to be tested must be enabled. Enable
the overcurrent elements for a particular winding with the EOC1, EOC2,
EOC3, and EOC4 settings for Windings 1, 2, 3, and 4 respectively. By setting
these to “Y” the overcurrent elements are enabled for the corresponding
winding. The pickup settings for each overcurrent element must also be set to
a pickup value. If they are not set to a value but are set to “OFF,” that
particular overcurrent element is disabled.
Instantaneous Overcurrent Elements
Step 1. Purpose: Determine the expected instantaneous overcurrent
element pickup value.
Method: Execute the
SHO
command via the relay front panel
or serial port and verify the setting (i.e.,
SHO 50P11P
<Enter>
).
Step 2. Purpose: Display the appropriate Relay Word bit on the front-
panel LEDs.
Method: Execute the
TARGET
command (i.e.,
TAR F 50P11
<Enter>
). The SEL-387 now displays the state of several
Winding 1 overcurrent elements on the bottom row of front-
panel LEDs.
Step 3. Purpose: Connect and apply a single current test source until
the appropriate LED illuminates.
Method:
a. Connect a single current test source (i.e., source 1) as
b. Turn on the current test source for the winding under
test, and slowly increase the magnitude of current
applied until the appropriate element asserts (i.e.,
50P11), causing the LED to illuminate (i.e., left-most).
Note the magnitude of the current applied. It should
equal the 50P1P setting ±5% of the setting ±0.02 I
NOM
(negative-sequence elements are ±6% of the setting
±0.02 I
NOM
).
Z01
Z02
IAW1
Z04
Z03
IBW1
Z06
Z05
ICW1
Z08
Z07
IAW2
Z10
Z09
IBW2
Z12
Z11
ICW2
Z14
Z13
IAW3
Z16
Z15
IBW3
Z18
ICW3
Z20
Z19
IAW4
Z22
IBW4
Z24
Z23
ICW4
C
B
A
SEL-387
(partial)
Current
Source 1
Current
Source 2
NOTE
: This example tests the
Winding 1 50P11 phase overcurrent
element. Use the same procedure to
test all instantaneous overcurrent
elements for each winding.
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...