4.40
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Control Logic
Relay Word Bits
50P31T
Winding 3 phase definite-time O/C Level 1 element timed out
10
50P32
Winding 3 phase instantaneous O/C Level 2 element picked
up
10
50P33
50A33 + 50B33 + 50C33
11
50P34
50A34 + 50B34 + 50C34
11
50P41
Winding 4 phase definite-time O/C Level 1 element picked up
14
50P41T
Winding 4 phase definite-time O/C Level 1 element timed out
14
50P42
Winding 4 phase instantaneous
O/C Level 2 element picked up
14
50P43
50A43 + 50B43 + 50C43
15
50P44
50A44 + 50B44 + 50C44
15
50Q11
Winding 1 neg.-seq. definite-time
O/C Level 1 element picked up
5
50Q11T
Winding 1 neg.-seq. definite-time O/C element timed out
5
50Q12
Winding 1 neg.-seq. instantaneous
O/C Level 2 element picked up
5
50Q21
Winding 2 neg.-seq. definite-time
O/C Level 1 element picked up
9
50Q21T
Winding 2 neg.-seq. definite-time
O/C Level 1 element timed out
9
50Q22
Winding 2 neg.-seq. instantaneous
O/C Level 2 element picked up
9
50Q31
Winding 3 neg.-seq. definite-time
O/C Level 1 element picked up
13
50Q31T
Winding 3 neg.-seq. definite-time
O/C Level 1 element timed out
13
50Q32
Winding 3 neg.-seq. instantaneous
O/C Level 2 element picked up
13
50Q41
Winding 4 neg.-seq. definite-time O/C element picked up
17
50Q41T
Winding 4 neg.-seq. definite-time O/C element timed out
17
50Q42
Winding 4 neg.-seq. instantaneous
O/C Level 2 element picked up
17
51N1
Winding 1 residual inverse-time O/C element picked up
4
51N1R
Winding 1 residual inverse-time O/C 51N1 element is reset
4
51N1T
Winding 1 residual inverse-time O/C element timed out
4
51N2
Winding 2 residual inverse-time O/C element picked up
8
51N2R
Winding 2 residual inverse-time O/C 51N2 element is reset
8
51N2T
Winding 2 residual inverse-time O/C element timed out
8
51N3
Winding 3 residual inverse-time O/C element picked up
12
51N3R
Winding 3 residual inverse-time O/C 51N3 element is reset
12
51N3T
Winding 3 residual inverse-time O/C element timed out
12
51N4
Winding 4 residual inverse-time O/C element picked up
16
51N4R
Winding 4 residual inverse-time O/C 51N4 element is reset
16
51N4T
Winding 4 residual inverse-time O/C element timed out
16
Table 4.11
Relay Word Bits Sorted Alphabetically
(Sheet 5 of 13)
Bit
Definition
Row
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...