10.27
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Testing and Troubleshooting
Acceptance Testing
Step 3. Purpose: Connect two current test sources to one phase of one
winding input.
Method:
a. Connect a current source to the
IAW1
input.
b. Connect a second current source in parallel with the
first source to the
IAW1
input as shown in
.
Step 4. Purpose: Apply fundamental current to pick up the 87R
element.
Method: Turn on the first current test source connected to the
Winding 1 input (
IAW1
) equal to the TAP1 setting multiplied by
the connection constant A shown in
. The
87R
LED
will illuminate once current is applied to the relay.
Step 5. Purpose: Apply and ramp second-harmonic current to dropout
the 87R element.
Method:
a. Turn on the second current source for second-harmonic
current (120 Hz for NFREQ = 60 and 100 Hz for
NFREQ = 50).
b. Starting at zero current, slowly increase the magnitude
of this second current source until the 87R element
deasserts, causing the 87R LED to completely
extinguish. Note the value of the applied current from
the second test source. The current from the second-
harmonic source should equal the PCT2 setting divided
by 100, multiplied by the magnitude of the fundamental
current source, ±5% and ±0.02 I
NOM
.
IAW1 (second harmonic) = PCT2/100 • IAW1
(fundamental), ±5% ± 0.02 I
NOM
Figure 10.7
Test Connections for Parallel Current Sources
Fifth-Harmonic Blocking
Step 1. Purpose: Verify the fifth-harmonic restraint percentage.
Method:
a. Execute the
SHOW
command via the relay front panel
or serial port and verify the percentage of fundamental
current that the magnitude of fifth-harmonic current
must exceed for differential restraint.
b. Enter
SHO PCT5 <Enter>
.
Z01
Z02
IAW1
Z04
IBW1
Z06
Z05
ICW1
Z08
IAW2
Z10
Z09
IBW2
Z12
Z11
ICW2
Z14
Z13
IAW3
Z16
Z15
IBW3
Z18
Z17
ICW3
Z20
Z19
IAW4
Z22
Z21
IBW4
Z24
Z23
ICW4
SEL-387
(partial)
Current
Source 1
Current
Source 2
NOTE:
This test requires a current
source capable of generating fifth-
harmonic current. This example tests
the fifth-harmonic blocking function.
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...