3.53
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Differential, Restricted Earth Fault, Thermal, and Overcurrent Elements
Overcurrent Element
input to the AND gate. The torque-control SEL
OGIC
control equation,
50Q
n
2TC, determines the other AND input. If 50Q
n
2TC is true, Relay Word
bit 50Q
n
2 asserts.
50Nn2 Residual Instantaneous Element
The 50N
n
2 element compares the magnitude of the calculated residual
current, IRW
n
, to the pickup setting, 50N
n
2P. If the calculated residual current
exceeds the pickup level, a logical 1 asserts at one input to the AND gate. The
torque-control SEL
OGIC
control equation, 50N
n
2TC, determines the other
AND input. If 50N
n
2TC is true, Relay Word bit 50N
n
2 asserts.
51Qn and 51Nn–Sequence Inverse-Time Elements
shows the logic for the inverse-time 51Q
n
negative-sequence
element and the inverse-time 51N
n
residual element.
Figure 3.24
51Qn and 51Nn Sequence Inverse-Time O/C Element,
Torque Controlled
51Qn Negative-Sequence Inverse-Time Element
The 51Q
n
element logic compares the magnitude of the calculated negative-
sequence current, 3I2W
n
, to the pickup setting, 51Q
n
P. If the calculated
negative-sequence current exceeds the pickup level, a logical 1 asserts at one
input to the AND gate at the center. The torque-control SEL
OGIC
control
equation, 51Q
n
TC, determines the other AND input. If 51Q
n
TC is true, Relay
Word bit 51P
n
asserts and the inverse curve begins timing.
As with phase inverse-time element logic, four settings define the curve. In
this case 51Q
n
P is the pickup, 51Q
n
C defines the curve equation, 51Q
n
TD
defines the time dial, and 51Q
n
RS determines how the curve resets.
Curve time-out causes Relay Word bit 51Q
n
T to assert. When the current
drops below pickup, 51Q
n
deasserts and the element resets according to the
setting for 51Q
n
RS. At the completion of the reset, Relay Word bit 51Q
n
R
asserts. This bit normally is at logic state 1, when the element is at rest during
normal system operation. You can use the
TAR
command to verify the state of
the bit. You can use the Level 2 serial port command
RES
or the front-panel
RESET51
function under the
{OTHER}
pushbutton to force the bit to a logical 1
during element testing. This saves time if you have chosen electromechanical
reset.
51Nn Residual Inverse-Time Element
The 51N
n
element compares the magnitude of the calculated residual current,
IRW
n
, to the pickup setting, 51N
n
P. If calculated residual current exceeds the
pickup level, a logical 1 asserts at one input to the AND gate at the center. The
Relay
Word
Bits
Relay
Word
Bits
(n = Winding 1, 2, 3, or 4)
51QnP (51NnP) (pickup)
51QnC (51NnC) (curve)
51QnTD (51NnTD) (time dial)
51QnRS (51NnRS) (E/M reset)
(1 cycle if RS = N,
curve if RS = Y)
Sequence
Current
Timing
+
–
(51Nn)
51Qn
51QnT (51NnT)
(curve timeout)
51QnR (51NnR)
(reset)
51QnTC (51NnTC)
(SEL
OGIC
control
equation TRUE)
|
3I2Wn
|
(
|
IRWn
|
)
51QnP (51NnP)
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...