Configuration Settings
Relay Identifier (39 Characters)
RID
=
XFMR 1
Terminal Identifier (59 Characters)
TID
=
STATION A
Enable Winding 1 in Differential Element (Y, N, Y1)
E87W1
=
Y
Enable Winding 2 in Differential Element (Y, N, Y1)
E87W2
=
Y
Enable Winding 3 in Differential Element (Y, N, Y1)
E87W3
=
Y
Enable Winding 4 in Differential Element (Y, N, Y1)
E87W4
=
N
Enable Winding 1 O/C Elements and Dmd Thresholds (Y, N)
EOC1
=
Y
Enable Winding 2 O/C Elements and Dmd Thresholds (Y, N)
EOC2
=
Y
Enable Winding 3 O/C Elements and Dmd Thresholds (Y, N)
EOC3
=
Y
Enable Winding 4 O/C Elements and Dmd Thresholds (Y, N)
EOC4
=
N
Enable Combined O/C Elements (Y, N)
EOCC
=
N
Enable Thermal Element (Y, N) (SEL-387-6 Relay only)
ETHER
=
Y
Enable RTDA Element (Y, N)
(SEL-387-5 and SEL-387-6 Relays only)
E49A
=
N
Enable RTDB Element (Y, N)
(SEL-387-5 and SEL-387-6 Relays only)
E49B
=
N
Enable SEL
OGIC®
Control Equations Set 1 (Y, N)
ESLS1
=
N
Enable SEL
OGIC
Control Equations Set 2 (Y, N)
ESLS2
=
N
Enable SEL
OGIC
Control Equations Set 3 (Y, N)
ESLS3
=
N
General Data
Winding 1 CT Connection (D, Y)
W1CT
=
Y
Winding 2 CT Connection (D, Y)
W2CT
=
Y
Winding 3 CT Connection (D, Y)
W3CT
=
Y
Winding 4 CT Connection (D, Y)
W4CT
=
Y
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...