7
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
SEL-387 Relay Command Summary
PAS 1
xxxxxx
Change Access Level 1 password to
xxxxxx
.
PAS B
xxxxxx
Change Access Level B password to
xxxxxx
.
PAS 2
xxxxxx
Change Access Level 2 password to
xxxxxx
.
If
xxxxxx
is
DISABLE
(uppercase), password for selected level is disabled.
PAS C
xxxxxx
Change Access Level C password to
xxxxxx
.
If
xxxxxx
is
DISABLE
(uppercase), password for selected level is disabled.
PUL
y k
Pulse output contact
y
(
y
= OUT101,…,OUT107, OUT2
XX
, and OUT3
XX
). Enter number
k
to pulse for
k
sec-
onds [
k
= 1 to 30 (seconds)], otherwise pulse time is 1 second. JMP6B has to be in place to enable this command.
QUI
Quit. Returns to Access Level 0. Returns front-panel LEDs to the default targets.
RES
RESET51
command resets all inverse-time O/C elements for the four windings, including the
Combined Overcurrent elements.
SER
d1
Show rows in the Sequential Events Recorder (SER) event report for date
d1
.
SER
d1 d2
Show rows in the Sequential Events Recorder (SER) event report from date
d1
to
d2
.
Entry of dates is dependent on the Date Format setting DATE_F (= MDY or YMD).
SER
m n
Show rows
m
through
n
in the Sequential Events Recorder (SER) event report.
SER
n
Show the latest
n
rows in the Sequential Events Recorder (SER) event report.
SER C
Clear the Sequential Events Recorder (SER) event reports from memory.
SET
n
Change relay group settings (overcurrent, differential, etc.). For the
SET
commands, parameter
n
is the setting
name at which to begin editing settings. If parameter
n
is not entered, setting editing starts at the first setting.
SET G
Change global settings.
SET P
n
Change port settings.
SET R
Change Sequential Events Recorder (SER) settings.
SHO
n
Show relay group
n
settings. Shows active group if
n
is not specified.
SHO G
Show relay global settings.
SHO P
Show port settings and identification of port to which user is connected.
SHO P
n
Show port settings for port
n
(
n
=1, 2, 3, 4).
SHO R
Show Sequential Events Recorder (SER) settings.
STA
Show relay self-test status.
TAR
n k
Show Relay Word row
n
status (
n
= 0 through 41). Enter number
k
to scroll Relay Word row
n
status
k
times on
screen.
Append F to display targets on the front panel, second row of LEDs.
TAR R
Return front-panel LED targets to regular operation and reset the tripping front-panel targets.
All commands that begin TFE apply to the SEL-387-5 and SEL-387-6 Relays
TFE
Displays cumulative and individual through-fault event data. The twenty (20) most recent individual events are
displayed.
TFE
n
Displays cumulative and individual through-fault event data. The
n
most recent individual events are displayed,
where
n
= 1 to 1200.
TFE A
Displays cumulative and individual through-fault event data. All the most recent individual events are
displayed, up to 1200.
TFE C
Clears/resets cumulative and individual through-fault event data.
TFE P
Preloads cumulative through-fault event data.
TFE R
Clears/resets cumulative and individual through-fault event data.
Access Level 2
Commands
The Access Level 2 commands primarily allow the user to change settings or operate relay
parameters and output contacts. All Access Level 1 commands can also be executed from Access
Level 2. The screen prompt is: =>>
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...