7.27
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Serial Port Communications and Commands
SEL ASCII Protocol Details
close, and all timers and relay elements reset. The relay logic is fully
functional while editing settings. The relay is only disabled for approximately
one second when settings are saved.
for all default settings and setting
worksheets.
SET G (Edit Global Settings)
Access Level 2
Configure the relay global settings using the
SET G
command. The global
settings include Event Report parameters, frequency, phase rotation, date
format, front-panel time-out, rotating display update rate, the group switching
time delay, DC battery monitor thresholds, breaker monitor settings, analog
input labels, SS
n
setting group variables, and definition of front-panel
programmable LED and Display Point variables. The entire syntax of the
SET
G
command follows:
SET G Setting TERSE <Enter>
The two parameters are optional and perform the following functions:
➤
Setting
specifies the setting name with which to begin. The
default is the first setting.
➤
TERSE
eliminates the display of the global settings at the end
of the setting procedure. The command will function properly
if just
TE
is entered, instead of the full word.
The
SET G
procedure works just like the
SET
procedure.
lists the
editing keys that you can use with the
SET
command.
for all default settings and setting
worksheets.
SET P (Edit Port Settings)
Access Level 2
Configure the relay port settings using the
SET P
command. The port settings
include the communication and protocol settings. The entire syntax of the
SET P
command follows:
SET P
n
Setting TERSE <Enter>
The two parameters are optional and perform the following functions:
➤
n
specifies the serial port number (1, 2, 3, or 4). Default is the
port issuing the command.
➤
Setting
specifies the setting name with which to begin. The
default is the first setting.
➤
TERSE
eliminates the display of the port settings at the end of
the setting procedure.
The command will function properly if just
TE
is entered, instead of the full
word.
The
SET P
procedure works just like the
SET
procedure.
lists the
editing keys that you can use with the
SET
command.
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...