H.21
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Protection Application Examples
Transformer Winding and CT Connection Compensation Settings Examples
The compensation settings of
assume that the Winding 1 side of the
transformer is connected to relay Terminal W1 and the Winding 2 side of the
transformer is connected to relay Terminal W2. These settings apply for all
standard phase-to-bushing connections shown in
. In each of these
phase-to-bushing connections, the order of the phase connections (A, B, C)
matches the order of the bushings (H1, H2, H3).
References
Further discussion on selecting transformer compensations settings can be
found in the technical paper,
Beyond the Nameplate – Selecting Transformer
Compensation Settings for Secure Differential Protection
by Barker Edwards,
David G. Williams, Ariana Hargrave, Matthew Watkins, and Vinod K. Yedidi.
YDAC/Yd1
11
0
YDAB/Yd11
1
0
DABDAB/Dd0
DACDAC/Dd0
0
0
YY/Yy0
11
11
Table H.4
Quick Settings Guide for Common Transformer Configurations and
Standard Connections
(Sheet 2 of 2)
XFMR Connection
W1CTC
(Winding 1)
W2CTC
(Winding 2)
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...