10.36
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Testing and Troubleshooting
Relay Troubleshooting
Self-Test Failure: +5 V PS
1. Power 5 V output out-of-tolerance.
See
STATUS
command.
2. A/D converter failure.
Self-Test Failure: +5 V REG
1. Reg5 V output out-of-tolerance. See
STATUS
command.
2. A/D converter failure.
Self-Test Failure: –5 V REG
1. Regulated –5 V output out-of-tolerance. See
STATUS
command.
2. A/D converter failure.
Self-Test Failure: +12 V PS
1. Power 12 V output out-of-
tolerance. See
STATUS
command.
2. A/D converter failure.
Self-Test Failure: –12 V PS
1. Power supply –12 V output out-of-
tolerance. See
STATUS
command.
2. A/D converter failure.
Self-Test Failure: +15 V PS
1. Power 15 V output out-of-
tolerance. See
STATUS
command.
2. A/D converter failure.
Self-Test Failure: -15 V PS
1. Power supply –15 V output out-of-
tolerance. See
STATUS
command.
2. A/D converter failure.
Self-Test Failure: Offset
1. Offset drift.
2. A/D converter drift.
3. Loose ribbon cable between transformers
and main board.
Self-Test Failure: ROM
1. Memory failure. Contact the factory.
Self-Test Failure: RAM
1. Failure of static RAM IC. Contact the
factory.
Table 10.5
Troubleshooting
(Sheet 3 of 4)
Symptom
Diagnosis/Solution
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...