H.10
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Protection Application Examples
Transformer Winding and CT Connection Compensation Settings Examples
Non-Standard CT Connections: Reversed CT Polarity.
shows the X-side CT polarity marks toward the transformer. However,
because the connections to the relay remain the same, the relay currents flow
the same, as in
. No additional adjustments need to be made
because of this type of non-standard CT connection.
Figure H.13
Current Flow With Reversed X-Side CT Polarity
Non-Standard CT Connections: Reversed CT Polarity and Reversed
Connections.
, the polarity marks of the X-side CTs are
, but the neutral sides of the CTs are
away from the transformer. With these connections, the H-side and X-side
currents are both entering the relay at the relay polarity mark.
B (H2)
C (H3)
A (H1)
Winding 1
Winding 2
A
B
C
a
b
c
SEL-387
(Partial)
IAW1
IBW1
ICW1
IAW2
IBW2
ICW2
H3
H2
H1
X3
X2
X1
IA System
Ia System
IA Relay
Ia Relay
c (X3)
b (X2)
a (X1)
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...