7.11
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Serial Port Communications and Commands
SEL ASCII Protocol Details
➤
RID and TID settings for the active group
➤
Date and time the event was triggered
➤
The event type
➤
Target information
➤
Phase currents for all four windings
Access Levels
Commands can be issued to the relay via the serial port to view metering
values, change relay settings, etc. The available ASCII serial port commands
are listed in
, and summarized by level in the
. A multilevel password system provides security against
unauthorized access. This access scheme allows you to give personnel access
to only those functions they require.
The relay supports four access levels. Each level has an associated screen
prompt and password. The relay is shipped with the default factory passwords
shown in the table under
. Below are the access
level hierarchy, the access level prompts, and commands allowed in each of
the four access levels:
summarizes the access levels, prompts, and commands available
from each access level and commands for moving between access levels.
The relay responds with
Invalid Access Level
if a command is entered from
an access level lower than the specified access level for the command. The
relay responds
Invalid Command
to commands not listed or if a command is
not followed by the correct number or letter.
Access Level 0
Once serial port communications are established with the relay, the Access
Level 0 prompt (
=
) appears. If a different prompt appears, the relay was left in
a different access level or the terminal emulation you are using is translating
the characters differently. VT 100 emulation is recommended.
The only commands that can be executed at Access Level 0 are the
ACC
and
QUI
commands (see
. Enter the
ACC
command at the Access Level
0 prompt to go to Access Level 1.
Access Level 1
After issuing the
ACC
command and entering the password, if it is required
[see
for default factory passwords], the relay is
in Access Level 1. The prompt for Access Level 1 appears (
=>
).
Access Level
Prompt
Commands Allowed
0 (lowest)
=
0
1
=>
0, 1
B
==>
0, B
2
=>>
0, 1, B, 2
C (highest)
==>>
0, 1, B, 2, C
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...