D.9
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Configuration, Fast Meter, and Fast Operate Commands
Message Definitions
A5D2/A5D3 Demand/
Peak Demand
In response to the A5D2 or A5D3 request, the relay sends the following block.
A5CE Fast Operate
In response to the A5CE request, the relay sends the following block.
495257340000 (IRW4)
02
FF
0000
00
Reserved
xx
Checksum
Table D.6
A5C2/A5C3 Demand/Peak Demand Fast Meter Configuration
Messages
(Sheet 4 of 4)
Data
Description
Table D.7
A5D2/A5D3 Demand/Peak Demand Fast Meter Message
Data
Description
A5D2 or A5D3
Command
A6
Message length (166 bytes)
00
Reserved
160 bytes
Demand meter values in double floats
in the same order as channel listings in A5C2.
00
Reserved
xx
Checksum
Table D.8
A5CE Fast Operate Configuration Block
(Sheet 1 of 3)
Data
Description
A5CE
Command
42
Message length, #bytes (66)
04
# circuit breakers supported
0010
16 remote bits
01
Remote bit pulse supported
00
Reserved
31
Open breaker 1
11
Close breaker 1
32
Open breaker 2
12
Close breaker 2
33
Open breaker 3
13
Close breaker 3
34
Open breaker 4
14
Close breaker 4
00
Clear remote bit RB1
20
Set remote bit RB1
40
Pulse remote bit RB1
01
Clear remote bit RB2
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...