10.17
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Testing and Troubleshooting
Acceptance Testing
e. Slowly reduce
IAW1
until the unit picks up, indicated by
LED A
. This should happen when
IAW1
equals CTR2/
CTR1 • (IAW2–51PC1P).
f.
After verifying pickup, increase
IAW1
back to IAW2 •
CTR2/CTR1.
LED A
will extinguish.
g. Wait for
LED C
to reappear, indicating reset. Or, issue
command
RES
to force a reset.
h. Suddenly reduce the current
IAW1
to a value equal to
CTR2/CTR1 • (IAW2–M • 51PC1P), where M is the
desired multiple of pickup.
i.
Allow the unit to proceed to time-out, indicated by the
lighting of
LED B
.
(
LED A
will also be lit.)
Step 4. (For CTR2<CTR1).
Purpose: Connect and apply two single current test sources to
create sufficient current to operate the 51PC1 element.
Method:
a. Connect two single current test sources as shown in
b. Set the
IAW1
current at some fixed value, such as 10 A at
angle zero degrees.
c. Set the
IAW2
current to a value equal to IAW1 • CTR1/
CTR2 at 180 degrees. Since the phasor sum is zero,
nothing will happen.
d. Execute the
TAR F 22
command. Relay Word bits
51PC1 and 51PC1T will appear in the second row of
LEDs, in the
A
and
B
positions, during the tests. Before
the test,
LED C
should be lit, representing bit 51PC1R
(reset).
e. Slowly reduce
IAW2
until the unit picks up, indicated by
LED
A
. This should happen when
IAW2
equals CTR1/
CTR2 • (IAW1–51PC1P).
f.
After verifying pickup, increase
IAW2
back to IAW1 •
CTR1/CTR2.
LED A
will extinguish.
g. Wait for
LED C
to reappear, indicating reset. Or, issue
command
RES
to force a reset.
h. Suddenly reduce the current
IAW2
to a value equal to
CTR1/CTR2 • (IAW1–M • 51PC1P), where M is the
desired multiple of pickup.
i.
Allow the unit to proceed to time-out, indicated by the
lighting of
LED B
.
(
LED A
will also be lit.)
Step 5. Purpose: Verify the operation time.
Method:
a. Type
SER <Enter>
to view the SER records. The
assertion and deassertion of each element listed in the
SER1, 2, 3, and 4 settings are recorded.
b. Subtract the time of the assertion of the pickup (i.e., 51PC1)
from the assertion time of the time-out bit (i.e., 51PC1T).
This is the operate time.
SER C
clears the SER records.
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...