8.14
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Front-Panel Interface
Pushbuttons
For example, suppose the local control switch with local bit output LB1 is
configured as an ON/OFF type switch (see
).
If power to the relay is turned off and then turned on again, local bit LB1
remains at logical 1. This is similar to a traditional panel, where enabling/
disabling of other functions is accomplished by panel-mounted switches. If dc
control voltage to the panel is lost and then restored, the switch positions are
still in place. If the switch is in the enable position (switch closed) before the
power outage, it will be in the same position when power is restored.
Pulse Output Contacts
Use the control pushbutton
{CNTRL}
to mimic the
PUL
se,
OPE
n, and
CLO
se
serial port commands. This is useful during relay checkout to verify that
output contacts actually function in response to a command.
Pulse Output Contacts
are available in the
{CNTRL}
menu after the Local Bit
pushbutton functions. The screen will prompt for
Pulse Close Open
. Use the
right/left arrow keys and
{SELECT}
to choose.
If
Pulse
is selected, the next screen will prompt for the output to be pulsed.
These are
OUT101
to
OUT107
and
ALARM
. Use the up/down arrow keys and
{SELECT}
to choose. The display will follow with a
Yes/No
verification request.
Again, use the up/down arrow keys and
{SELECT}
to choose.
The relay will pulse the output contact for one second then return to the
contact selection screen in case there are more contacts to test.
{CANCEL}
will
return to the main
CNTRL
menu.
{EXIT}
will abort the command and return to
the default display.
If
Close
is selected, the next screen prompts for the breaker (Bk1 to Bk4) to be
closed. Use the right/left arrow keys and
{SELECT}
to choose, for example Bk1.
The relay then asks
Close Bkr 1? Yes No
. Use the right/left arrow keys and
{SELECT}
to choose. If
Yes
, the relay asserts the CC1 Relay Word bit. If CC1
has been assigned to the CL1 Close Logic setting, the breaker will close. If
No
is selected, the relay returns to the
Close
menu.
If
Open
is selected, a sequence exactly like the one for
Close
takes place. If
Yes
is selected, the relay assert Relay Word bit OC1 for Bkr 1, and if this bit
has been assigned to the TR1 Trip Logic setting, the breaker will open. The
TRIP
front-panel LED will also light. It can be turned off by pushing the
{TARGET RESET}
pushbutton or by the
TAR R
serial port command.
Since all three
{CNTRL}
functions are legitimate event types, an Event Report
will be triggered whenever any is activated. An automatic message will be
sent to any port set to receive messages. If the contact outputs are listed as
SER triggers, the contact assertion and deassertion will appear in the SER
report, with time tags. Contact operate timing can thus be easily analyzed.
GROUP
The
{GROUP}
function is identical to the
GRO
and
GRO
n
(
n
= 1 to 6) serial
port commands.
Logical 1
LB1
Relay
Word
Bit
Enable
FAN CONTROL
Disable
(logical 0)
NOTE:
The
{CNTRL}
function, while
useful during testing, should not be
used while the relay is actually in
service. During the one-second
interval while contact
OUT10X
is being
pulsed, all other
OUT10Y
contacts are
frozen in their existing state and are
not permitted to change. This could
prevent a trip or other vital output
from being issued during the pulse
interval.
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...