B.4
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
SEL-300 Series Relays Firmware Upgrade Instructions
Upgrade Procedure
b. Click
OK
.
Figure B.3
Determining Communications Parameters for the Computer
Step 7. Set the terminal emulation to VT100:
a. From the
File
menu, choose
Properties
.
b. Select the
Settings
tab in the
Firmware Upgrade
Properties
dialog box (
).
c. Select
VT100
from the
Emulation:
list box and click
OK
.
Figure B.4
Setting Terminal Emulation
Step 8. Confirm serial communication.
Press
<Enter>
. In the terminal emulation window, you should
see the Access Level 0
=
If this is successful, proceed to
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...