10.13
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Testing and Troubleshooting
Acceptance Testing
Step 5. Purpose: Repeat the test for each definite-time and inverse-time
overcurrent element, for each winding.
Method:
a. Repeat
through
listed in
for each winding.
b. Remember to set the SER for the appropriate elements
and apply current to the appropriate winding.
Phase Overcurrent Elements
The SEL-387 has many phase overcurrent elements. They all operate based on
a comparison between the phase current directly applied to the winding inputs
and the phase overcurrent setting. The elements that have a P as the third
character of the element name operate when any one of the three phase
currents exceeds the phase current setting threshold. The elements that have
an A, B, or C as the third character in the element name operate based on that
phase current.
Test the instantaneous and time-delayed phase overcurrent elements by
applying current to the inputs and comparing relay operation to the phase
overcurrent settings. These tests were previously outlined in this section.
Table 10.3
Time-Delayed Overcurrent Elements and Corresponding Settings
Winding 1
Winding 2
Winding 3
Winding 4
Bit
Setting
Bit
Setting
Bit
Setting
Bit
Setting
Phase
Level
1
50P11 50P11P
50P21 50P21P
50P31 50P31P
50P41 50P41P
Definite-Time
50P11T 50P11D
50P21T 50P21D
50P31T 50P31D
50P41T 50P41D
Phase
Inverse-Time
51P1 51P1P
51P2 51P2P
51P3 51P3P
51P4 51P4P
Curve
51P1C
51P2C
51P3C
51P4C
Time-Dial
51P1TD
51P2TD
51P3TD
51P4TD
Time-Out
51P1T
51P2T
51P3T
51P4T
Residual Level 1
50N11
50N11P
50N21
50N21P
50N31
50N31P
50N41
50N41P
Definite-Time
50N11T 50N11D
50N21T 50N21D
50N31T 50N31D
50N41T 50N41D
Residual
Inverse-Time
51N1 51N1P
51N2 51N2P
51N3 51N3P
51N4 51N4P
Curve
51N1C
51N2C
51N3C
51N4C
Time-Dial
51N1TD
51N2TD
51N3TD
51N4TD
Time-Out
51N1T
51N2T
51N3T
51N4T
Neg-Seq Level 1
50Q11
50Q11P
50Q21
50Q21P
50Q31
50Q31P
50Q41
50Q41P
Definite-Time
50Q11T 50Q11D
50Q21T 50Q21D
50Q31T 50Q31D
50Q41T 50Q41D
Neg-Seq
Inv-Time
51Q1 51Q1P
51Q2 51Q2P
51Q3 51Q3P
51Q4 51Q4P
Curve
51Q1C
51Q2C
51Q3C
51Q4C
Time-Dial
51Q1TD
51Q2TD
51Q3TD
51Q4TD
Time-Out
51Q1T
51Q2T
51Q3T
51Q4T
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...