5.25
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Metering and Monitoring
Status Monitor
Table 5.4
Self-Test Alarm Limits
Self-Test
Warning Limits
Failure Limits
Channel Offset
30 mVdc
NA
+5 V Power Supply
4.80/5.20 Vdc
4.65/5.40 Vdc
+5 V Regulated
4.75/5.20 Vdc
4.50/5.40 Vdc
–5 V Regulated
–4.75/–5.25 Vdc
–4.50/v5.40 Vdc
+12 V Power Supply
11.50/12.50 Vdc
11.20/14.00 Vdc
–12 V Power Supply
–11.50/–12.50 Vdc
–11.20/–14.00 Vdc
+15 V Power Supply
14.40/15.60 Vdc
14.00/16.00 Vdc
–15 V Power Supply
–14.40/–15.60 Vdc
–14.00/–16.00 Vdc
Temperature
–40/+85°C
–50/+100°C
RAM
NA
Cannot READ/WRITE
Flash ROM
NA
Bad Checksum
A/D
NA
Slow Conversion
Critical RAM
NA
Bad Checksum
EEPROM
NA
Bad Checksum
IO_BRD
NA
Incorrect Interface Board Value