SD300
POWER ELECTRONICS
236
MODBUS COMMUNICATION
Control Parameters
NOTE
: These parameters are read and write.
Modbus Address
Parameter
Scale Units
Values
Decimal Hexadecimal
40896
0h0380
Frequency
command
0.01
Hz
Frequency command setting
40897
0h0381
Rpm command
1
rpm
Rpm command setting
40898
0h0382
Operation command -
-
Bit 0
0: Stop command
1: Run command
Bit 1
0: Reverse command
1: Forward command
Bit 2: 0
→
1: Trip initialization
Bit 3: 0
→
1: Free-run stop
40899
0h0383
Acceleration time
0.1
s
Acceleration time setting
40900
0h0384
Deceleration time
0.1
s
Deceleration time setting
40901
0h0385
Communications
addresses control
(0: Off, 1: On)
Bit 0: Input 1 (CM.70)
Bit 1: Input 2 (CM.71)
Bit 2: Input 3 (CM.72)
Bit 3: Input 4 (CM.73)
Bit 4: Input 5 (CM.74)
Bit 5: Input 6 (CM.75)
Bit 6: Input 7 (CM.76)
Bit 7: Input 8 (CM.77)
40902
0h0386
Digital outputs
control
(0: Off, 1: On)
Bit 0: Relay 1
Bit 1: Multi-function output
40904
0h0388
PID reference
0.1
%
PID reference command
40905
0h0389
PID feedback
0.1
%
PID feedback value
40906
0h038A
Motor rated current 0.1
A
-
40907
0h038B
Motor rated voltage 1
V
-
40912
0h0390
Torque reference
0.1
%
Torque command
40913
0h0391
Torque limit positive
forward
0.1
%
Torque limit in forward
direction
40914
0h0392
Torque limit
negative forward
0.1
%
Regenerative torque limit in
forward direction
40915
0h0393
Torque limit positive
reverse
0.1
%
Torque limit in reverse
direction
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......