Parameter
Default
value
Description
Set value
dr.15
0
Torque boost
0:
Manual torque (Both directions can be
configured separately, in dr.16
➔
‘Start torque in
forward direction’ and in dr.17
➔
‘Start torque in
reverse direction’).
1 and 2:
The drive automatically calculates the
voltage to apply at the start using the motor
parameters.
dr.18
60.00Hz Motor frequency
50.00Hz
dr.19
0.50Hz Start frequency
0.10Hz
dr.20
60.00Hz Max speed limit
50.00Hz
dr.93
0
Parameter initialization
1:
Set parameters back to their factory value
(only if required).
dr.97
2.x
Software version
-
Cn.4
3kHz Modulation frequency 5kHz
In.1
50.00Hz Analog input max. freq 50.00Hz
In.7
10
V1 filter
10ms (Low Pass Filter for V1).
In.8
0V
V1 minimum voltage
0.00V (V1 minimum voltage adjustment).
In.9
0.00
V1 minimum reference 0.00 (% of the value set in In.1)
In.10
10V
V1 maximum voltage
10.0V (V1 maximum voltage adjustment).
In.11
100.00 V1 maximum reference 100.00 (% of the value set in In.1)
In.52
10ms I2 filter
10ms (Analogue input current filter).
In.53
4.00mA I2 minimum current
4.00mA (I2 minimum current adjustment).
In.54
0.00
I2 minimum reference 0.00 (% of the value set In.1)
In.55
20.00mA I2 maximum current
20.00mA (I2 maximum current adjustment)
In.56
100.00 I2 maximum reference 100.00 (% of the value set In.1)
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......