POWER ELECTRONICS
SD300
MODBUS COMMUNICATION
263
Screen
Description
Modbus
Decimal
Address
Hexadecimal
Range
Modbus Range
Pr.33
No motor fault delay
46945
0h1B21
0.1 to 10.0s
1 to 100
Pr.40
Action in case of
thermo-electronic fault
46952
0h1B28
None
Free-Run
Dec
0
1
2
Pr.41
Motor cooling mode at
zero speed
46953
0h1B29
SELF
FORCED
0
1
Pr.42
Overcurrent level
during 1min
46954
0h1B2A
120 to 200%
120 to 200
Pr.43
Continuous
overcurrent level
46955
0h1B2B
50 to 150%
50 to 150
Pr.45
Free run trip mode
46957
0h1B2D
FreeRun
Dec
0
1
Pr.50
Stall prevention
46962
0h1B32
Accelerating
At constant speed
At deceleration
FluxBraking
00
01
10
11
Pr.51
Speed for stall
protection 1
46963
0h1B33
dr.19 to Pr.53 Hz
dr.19 to Pr.53
Pr.52
Level for stall
protection 1
46964
0h1B34
30 to 250%
30 to 250
Pr.53
Speed for stall
protection 2
46965
0h1B35
In.55 to Pr.55 Hz
In.55 to Pr.55
Pr.54
Level for stall
protection 2
46966
0h1B36
30 to 250%
30 to 250
Pr.55
Speed for stall
protection 3
46967
0h1B37
In.53 to Pr.57 Hz
In.53 to Pr.57
Pr.56
Level for stall
protection 3
46968
0h1B38
30 to 250%
30 to 250
Pr.57
Speed for stall
protection 4
46969
0h1B39
In.55 to dr.20 Hz
In.55 to dr.20
Pr.58
Level for stall
protection 4
46970
0h1B3A
30 to 250%
30 to 250
Pr.59
Flux braking gain
46971
0h1B3B
0 to 150%
0 to 150
Pr.60
CAP diagnosis level
46972
0h1B3C
0 to 100%
0 to 100
Pr.61
Capacitor diagnosis
mode
46973
0h1B3D
Nonde
RefDiag
PreDiag
InitDiag
0
1
2
3
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......