SD300
POWER ELECTRONICS
300
COMMONLY USED CONFIGURATIONS
Programmed
frequency
Parameter
High speed
(P7)
Medium
speed (P6)
Low speed
(P5)
50.00Hz
0.00
0
0
0
30.00Hz
St1
0
0
1
35.00Hz
St2
0
1
0
40.00Hz
St3
0
1
1
45.00Hz
bA.53
1
0
0
50.00Hz
bA.54
1
0
1
47.00Hz
bA.55
1
1
0
42.00Hz
bA.56
1
1
1
Connection scheme
Terminals CM/P1: Start command (NO state).
Terminals CM/P5: Low speed (Low bit) (NO state).
Terminals CM/P6: Medium speed (Medium bit) (NO state).
Terminals CM/P7: High speed (High bit) (NO state).
Multi-speed commands (multi-step frequencies) using P5, P6 and P7