POWER ELECTRONICS
SD300
MODBUS COMMUNICATION
245
Screen
Description
Modbus
Decimal
Address
Hexadecimal
Range
Modbus Range
Ad.27
Jump frequency
activation
44891
0h131B
NO
SI
0
1
Ad.28
Lower limit jump freq.
1
44892
0h131C
0.00 to dr.29
0 to dr.29
Ad.29
Upper limit jump freq.
1
44893
0h131D
Ad.28 to dr.20
Ad.28 to dr.20
Ad.30
Lower limit jump freq.
2
44894
0h131E
0.00 to dr.31
0 to dr.31
Ad.31
Upper limit jump freq.
2
44895
0h131F
Ad.30 to dr.20
Ad.30 to dr.20
Ad.32
Lower limit jump freq.
3
44896
0h1320
0.00 to dr.33
0 to dr.33
Ad.33
Upper limit jump freq.
3
44897
0h1321
Ad.32 to dr.20
Ad.32 to dr.20
Ad.41
Open brake current
44905
0h1329
0.0 to 180.0%
0 to 1800
Ad.42
Delay before brake
opening
44906
0h132A
0.00 to 10.00s
0 to 1000
Ad.44
Brake opening forward
freq.
44908
0h132C
0.00 to dr.20
0 to dr.20
Ad.45
Brake opening reverse
freq.
44909
0h132D
0.00 to dr.20
0 to dr.20
Ad.46
Delay before brake
closing
44910
0h132E
0.00 to 10.00s
0 to 1000
Ad.47
Brake closing
frequency
44911
0h132F
0.00 to dr.20
0 to dr.20
Ad.50
Minimum flux mode
44914
0h1332
NONE
MANU
AUTO
0
1
2
Ad.51
Min. flux level in
manual mode
44915
0h1333
0 to 30%
0 to 30
Ad.60
Acceleration dwell
frequency
44924
0h133C
0.00 to dr.20
0 to dr.20
Ad.64
Fan operating mode
44928
0h1340
DuringRun
Always ON
Temp Ctrl
0
1
2
Ad.65
Save motorized
potentiometer
frequency
44929
0h1341
N
Y
0
1
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......