SD300
POWER ELECTRONICS
304
COMMONLY USED CONFIGURATIONS
Speed control (up/down potentiometer) and
Start/Stop commands by terminals
Parameter configuration
Parameter Default
value
Description
Set value
0.00
0.00Hz Frequency reference
x.xxHz (Reference visualization).
ACC
20.0 seg Acceleration time
10.0 sec
dEC
30.0 seg Deceleration time
10.0 sec
drv
1
Start/Stop control
1:
Start/Stop from terminals FX
–
Forward o Rx
–
Reverse.
Frq
0
Frequency setting mode
0:
Local
Ad.8
0
Stop mode
0:
Stop with deceleration ramp.
1:
DC brake to stop.
2:
Free run to stop.
4:
Regenerative brake to stop.
Ad.10
0
Start after low voltage.
0:
NO (Drive does not start after power loss).
1:
YES (Drive starts after power loss).
Ad.24
0
Use frequency limit
0:
NO (Limits are set by maximum frequency and
start frequency).
1:
YES (Limits are set by the higher and lower
frequency limits).
Ad.25
0.50Hz Frequency lower limit
0.00Hz
Ad.26
50.00Hz Frequency higher limit 50.00Hz
bA.13
(*)
Motor Current
?A (See motor plate).
dr.14
(*)
Motor rated power
0.2
0.2kW
…
…
5.5
5.5kW
7.5
7.5kW
dr.15
0
Torque boost
0:
Manual torque (Both directions can be
configured separately, in dr.16
➔
‘Start torque in
forward direction’ and in dr.17
➔
‘Start torque in
reverse direction’).
1 and 2:
The drive automatically calculates the
voltage to apply at the start using the motor
parameters.
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......