POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
113
Screen Description Default
value
Range
Function
Set
on
RUN
dr.81
Select
monitor code
Volt V
0 to 2
Select the monitor code.
OPT. DESCR. FUNCTION
0
Volt V
Scalar control mode. Drive
carries out the control
applying a voltage /
frequency ramp to the
motor.
1
Pot kW
Control by power.
2
Tq kgf
Control by torque.
YES
dr.89
Display
changed
parameters
All
All
Chang
Displays all parameters that are different from
the factory default values. Use this feature to
track changed parameters.
OPT. DESCR. FUNCTION
0
All
Display all parameters.
1
Chang
Display
changed
parameters.
YES
dr.90
ESC key
function
Mov.
Pos. In
0 to 2
The [ESC] key is a multi-functional key that can
be configured to carry out a number of different
functions.
OPT. DESCR. FUNCTION
0
Mov. Pos.
In.
Move to the initial position.
1
JOG Key Perform a jog operation.
2
Local/Rem.
Change from Local to
remote control if the key
has
previously
been
configured as such.
NO
Eloader
function
None
0 to 2
Set Eloader function.
OPT. DESCR. FUNCTION
0
None
No actions are executed.
1
Download Download upgrade file.
2
Upload
Store drive current values.
NO
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......