DESCRIPTION OF PROGRAMMING PARAMETERS
Screen Description Default
value
Range
Function
Set
on
RUN
bA.8
Acceleration
ramp type
MaxFreq
MaxFreq
FrqDelta
Enables the acceleration ramp setting:
OPT. DESCR. FUNCTION
0
MaxFreq
Allows accelerating or
decelerating with the same
ramp based on the
maximum
frequency,
independently from the
operating frequency.
1
FrqDelta
Allows
defining
the
accelerating/decelerating
time which will reach the
next speed reference
when working at constant
speed.
NO
bA.9
Time scale
01s
0.01s
0.1s
1s
Set the time scale for all time-related values. It
is particularly useful when a more accurate
Acc/Dec times are required because of load
characteristics, or when the maximum time
range needs to be extended.
OPT. DESCR. FUNCTION
0
0.01s
minimum unit: 0.01 s
1
0.1s
minimum unit: 0.1 s
2
1s
minimum unit: 1 s
NO
bA.10
Input
Frequency
60Hz
60Hz
50Hz
Set the input frequency. If the frequency
changes, so do all related settings (base
frequency, maximum frequency…).
OPT. DESCR. FUNCTION
0
60Hz
Set drive frequency to
60Hz.
1
50Hz
Set drive frequency to
50Hz.
NO
bA.11
Pole Number
(*)
2 to 48
Set the number of poles in the motor
according to its nameplate.
NO
bA.12
Rated Slip
(*)
0 to 3000rpm
When a heavy load produces a big slip during
the start, configure this parameter to
compensate the motor slip.
NO
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......