MODBUS COMMUNICATION
Screen
Description
Modbus
Decimal
Address
Hexadecimal
Range
Modbus Range
Ad.66
Select comparator
source
44930
0h1342
None
V1
V2
I2
Pulse
0
1
3
4
6
Ad.67
Output activation level
comparator mode
44931
0h1343
Ad.68 a 100.00
Ad.68 a 10000
Ad.68
Output deactivation
level comparator mode
44932
0h1344
-100.00 a Ad.67
-10000 a Ad.67
Ad.70
Safe operation
selection
44934
0h1346
Always Enable
DI Dependent
0
1
Ad.71
Safe operation stop
44935
0h1347
Free-Run
Q-Stop
Q-Stop Res
0
1
2
Ad.72
Q-Stop Time
44936
0h1348
0.0 to 600.0s
0 to 6000
Ad.74
Enable regeneration
prevention
44938
0h134A
NO
YES
0
1
Ad.75
Regeneration
prevention level
44939
0h134B
300 to 400V
600 to 800V
300 to 400
600 to 800
Ad.76
Compare frequency
limit
44940
0h134C
0.00 to 10.00Hz
0 to 1000
Ad.77
P gain regeneration
prevention
44941
0h134D
0.0 to 100.0%
0 to 1000
Ad.78
I gain regeneration
prevention
44942
0h134E
0.0 to 3000.0ms
0 to 30000
Ad.80
Fire mode selection
44944
0h1350
None
Fire Mode
Fire Mode Test
0
1
2
Ad.81
Fire mode frequency
44945
0h1351
0.00 to 60.00Hz
0 to 6000
Ad.82
Fire mode direction
44946
0h1352
Forward
Reverse
0
1
Cn.4
Modulation frequency
45124
0h1404
0.7 to 15.0
7 to 150
Cn.5
Modulation mode
45125
0h1405
Normal PWM
LowLeakage PWM
0
1
Cn.9
Pre-excitation time
45129
0h1409
0.00 to 60.00s
0 to 6000
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......