SD300
POWER ELECTRONICS
158
DESCRIPTION OF PROGRAMMING PARAMETERS
Group 5: Inputs
→
In
Screen Description Default
value
Range
Function
Set
on
RUN
In.1
Analog input
max. freq
dr.20
dr.19 to
dr.20
Set drive operating frequency for the
maximum voltage input of the analog input.
YES
In.2
Analog input
max. torque 100.0%
0.0 to
200.0% Reserved.
YES
In.5
V1 Monitor
0.00V
0.00 to
12.00 Voltage analog input 1 (V1) visualization.
NO
In.6
V1 polarity
0-10V
0-10V
-/+10V
This parameter allows setting the operation
directions of the drive:
DESCR. FUNCTION
0-10V Unipolar (forward operation)
10V
Bipolar (forward and reverse
operation directions)
NO
In.7
V1 filter
10ms
0 to
10000m
s
Low Pass Filter for V1. Allows setting the time
response to a change produced in the speed
reference, to reduce the speed fluctuation due
to unstable signs or noise. Thus, the response
becomes slower.
YES
In.8
V1 minimum
voltage
0.00V
0.00 to
10.00V
Define the minimum voltage for the analog
input 1 according to the connected sensor
characteristics
YES
In.9
V1 minimum
reference
0.00%
0.00 to
100.00%
Set the speed reference corresponding to the
analog input 1 minimum negative range. It
corresponds to the minimum voltage level set
in In.12. It is configured to introduce the speed
reference through the AI. The value is a
percentage of the frequency set in In.1.
YES
In.10
V1 maximum
voltage
10.00V 0.00 to
10.00V
Define the maximum voltage for the analog
input 1, according to the connected sensor
characteristics.
YES
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......