DESCRIPTION OF PROGRAMMING PARAMETERS
119
Screen Description Default
value
Range
Function
Set
on
RUN
bA.6
Alternative
torque
reference
LOCAL
Note:
comes from the previous page
.
OPT.
DESCR.
FUNCTION
6
MODBUS
The reference will be
introduced
through
Modbus.
8
COMMS
The reference will be
introduced
through
communications.
9
PLC
The common area can
be linked with user
sequence output and
can
be
used
as
command.
12
PULSE
Reference
will
be
introduced through the
Pulse input.
YES
bA.7
V/F Pattern
Linear
0 to 3
Set the alternative acceleration ramp.
OPT. DESCR. FUNCTION
0
Linear
Output voltage increases
and decreases at constant
rate
proportional
to
voltage/frequency
(V/F)
relation. Used to achieve a
constant
torque
load
regardless the frequency.
1
Square
Output voltage increases
quadratically
with
a
proportion of 1.5.
2
V/F Us Define a customized V/F
pattern.
3
Square2
Output voltage increases
quadratically with a
proportion of 2.
NO
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......