POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
191
Screen Description
Default
value
Range
Function
Set on
RUN
AP.24
PID controller
differential
time
0ms
0 to
10000ms
Set the regulator differential time. Whenever
a greater response is needed, this value can
be increased.
Note:
Increasing too much this value can
cause a precision loss.
YES
AP.25
PID output
fine
adjustment
+0.0%
0.0 to
1000.0%
Apply a fine adjustment at the PID output.
Use this parameter when an adjustment for
the proportional constant below 0.1% is
required.
YES
AP.26
Proportional
gain scale
100.0% 0.0 to
100.0%
This parameter, along with AP.22 allow
setting output ratio for errors between
reference and feedback. If AP.22 is set to
50%, then 50% of the error is output. For
ratios below 0.1% use AP.26.
NO
AP.27
PID Filter
0ms
0 to
10000ms
Used when the output of the PID controller
changes too fast or the entire system is
unstable, due to severe oscillation. In
general, a lower value (default value=0) is
used to speed up response time, but in
some cases a higher value increases
stability. The higher the value, the more
stable the PID controller output is, but the
slower the response time.
YES
AP.28
PID mode
Process
Process
Normal
Set PID Mode.
OPT. FUNCTION
0
Process
1
Normal
NO
AP.29
Upper limit
PID output
+60.00
Hz
AP.30 to
300.00
Hz
Set the PID output upper limit.
YES
AP.30
Lower limit
PID output
-60.00Hz
-300.00
Hz to
AP.29
Set the PID output lower limit.
YES
[32] Displayed when AP.1 is set to 2 (Proc PID).
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......