Screen Description
Default
value
Range
Function
Set on
RUN
Cn.80
KEB
proportional
gain
10000
1 to
20000
Maintain the voltage of the DC power
section during the kinetic energy buffering
operation. Change the setting value when a
low voltage trip occurs right after a power
failure.
YES
Cn.81
KEB integral
gain
500
[22]
1 to
20000
Maintain the voltage of the DC power
section during the kinetic energy buffering
operation. Sets the gain value to maintain
the frequency during the kinetic energy
buffering operation until the drive stops.
YES
Cn.82
Energy
buffering Slip
gain
30.0
0 to
2000.0%
Regulation of KEB function. Slip gain KEB. YES
Cn.83
Energy
buffering
acceleration
time
10.0
0.0 to
600.0 s
Regulation of KEB function. Acceleration
time KEB.
YES
Cn.85
[23]
Flux
proportional
gain 1
370
100 to
700
Flux estimator proportional gain 1.
YES
Cn.86
Flux
proportional
gain 2
0
0 to 100 Flux estimator proportional gain 2.
YES
Cn.87
Flux
proportional
gain 3
100
0 to 500 Flux estimator proportional gain 3.
YES
Cn.88
Flux integral
gain 1
50
[23]
0 to 200 Flux estimator integral gain 1.
YES
Cn.89
Flux integral
gain 2
50
[24]
0 to 200 Flux estimator integral gain 2.
YES
Cn.90
Flux integral
gain 3
50
[24]
0 to 200 Flux estimator integral gain 3.
YES
[22] Displayed when Cn.77 is not set to 0 (NO).
[23] Displayed when Cn.20 is set to 1 (YES).
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......