POWER ELECTRONICS
SD300
MODBUS COMMUNICATION
249
Screen
Description
Modbus
Decimal
Address
Hexadecimal
Range
Modbus Range
Cn.46
Initial pole position
estimation type
45172
0h1434
0
–
2
0
–
2
Cn.48
Controller P gain
45168
0h1430
10 to 10000
10 to 10000
Cn.49
Controller I gain
45169
0h1431
10 to 10000
10 to 10000
Cn.50
Voltage controller limit
45170
0h1432
0
–
1000%
0
–
1000
Cn.51
Voltage controller I
gain
45171
0h1433
0
–
20000%
0
–
20000
Cn.52
Output filter vector
45172
0h1434
0 to 2000ms
0 to 2000
Cn.53
Torque limit reference
45173
0h1435
LOCAL
V1
V2
I2
MDBUS
COMMS
PLC
Pulse
0
2
4
5
6
8
9
12
Cn.54
Forward positive
torque limit
45174
0h1436
0.0 to 200.0%
0 to 2000
Cn.55
Forward negative
torque limit
45175
0h1437
0.0 to 200.0%
0 to 2000
Cn.56
Reverse positive
torque limit
45176
0h1438
0.0 to 200.0%
0 to 2000
Cn.57
Reverse negative
torque limit
45177
0h1439
0.0 to 200.0%
0 to 2000
Cn.62
Speed limit reference
45182
0h143E
LOCAL
V1
V2
I2
MDBUS
COMMS
PLC
0
2
4
5
6
7
8
Cn.63
Forward speed limit
45183
0h143F
0.00 to 400.00Hz
0 to 40000
Cn.64
Reverse speed limit
45184
0h1440
0.00 to 400.00Hz
0 to 40000
Cn.65
Speed limit gain
45185
0h1441
100 to 5000%
100 to 5000
Cn.70
Speed search mode
selection
45190
0h1446
Flying Start1
Flying Start2
0
1
Cn.71
Search mode
45191
0h1447
00 to 15
0 to 15
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......