SD300
POWER ELECTRONICS
250
MODBUS COMMUNICATION
Screen
Description
Modbus
Decimal
Address
Hexadecimal
Range
Modbus Range
Cn.72
]
Speed search mode
current
45192
0h1448
80 to 200%
80 to 200
Cn.73
Speed search mode
prop. gain
45193
0h1449
0 to 9999
0 to 9999
Cn.74
Speed search integral
gain
45194
0h144A
0 to 9999
0 to 9999
Cn.75
Speed search delay
45195
0h144B
0.0 to 60.0s
0 to 600
Cn.76
Speed estimator gain
45196
0h144C
50 to 150%
50 to 150
Cn.77
KEB Select
45197
0h144D
No
KEB1
KEB2
0
1
2
Cn.78
Initial value for KEB
operation
45198
0h144E
110.0 to 200.0%
1100 to 2000
Cn.79
Value to stop KEB
operation
45199
0h144F
Cn.78 to 210.0%
Cn.78 to 2100
Cn.80
KEB proportional gain
45200
0h1450
1 to 20000
1 to 20000
Cn.81
KEB integral gain
45201
0h1451
1 to 20000
1 to 20000
Cn.82
Energy buffering slip
gain
45202
0h1452
0 to 2000.0%
0 to 20000
Cn.83
Energy buffering
acceleration time
45203
0h1453
0.0 to 600.0 s
0 to 6000
Cn.85
Flux proportional gain
1
45205
0h1455
100 to 700
100 to 700
Cn.86
Flux proportional gain
2
45206
0h1456
0 to 100
0 to 100
Cn.87
Flux proportional gain
3
45207
0h1457
0 to 500
0 to 500
Cn.88
Flux integral gain 1
45208
0h1458
0 to 200
0 to 200
Cn.89
Flux integral gain 2
45209
0h1459
0 to 200
0 to 200
Cn.90
Flux integral gain 3
45210
0h145A
0 to 200
0 to 200
Cn.91
SL voltage
compensation 1
45211
0h145B
0 to 60
0 to 60
Cn.92
SL voltage
compensation 2
45212
0h145C
0 to 60
0 to 60
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......