SD300
POWER ELECTRONICS
310
COMMONLY USED CONFIGURATIONS
When Cn.46 is set to 1 (Angle Detect), the motor is operated according to
the pole position detected by changes in the current. The voltage pulse
input is used to detect the pole position and it results in a small amount of
noise at motor startup.
When Cn. 46 is set to 2 (Alignment), the drive forcefully align the rotor
position by supplying DC current for a certain period of time.
Parameter Default
value
Description
Set value
Cn.35
2
Initial pole position estimation retry
2
Cn.36
20ms
Initial pole position estimation interval
20ms
Cn.37
15%
Initial pole position estimation pulse current (%) 15%
Cn.38
500%
Initial pole position estimation pulse voltage (%) 500%
Cn.46
1: Det. de
ángulo
Initial pole position estimation type
1: Det. de
ángulo
6.
Voltage compensation
These parameters set the output compensation values during a PM
synchronous motor operation in sensorless vector control mode.
If the motor fails operating at low speeds, at or below 5% of the rated motor
speed, increase the parameter values set at Cn.39 and Cn.40 by 10%
increments. Decrease the values in 10% decrements if a clanking noise
occurs at motor startup and motor stop.
Parameter
Default value
Description
Set value
Cn.39
100.0%
PM dead-time range (%)
100.0%
Cn.40
100.0%
PM dead-time voltage (%)
100.0%
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......