206
DESCRIPTION OF PROGRAMMING PARAMETERS
Screen Description
Default
value
Range
Function
Set on
RUN
Pr.89
CAP fan
status
0
00 to 11
Shows the status of capacitor fans.
OPT. DESCR. FUNCTION
00
None
There are no warnings
neither in the capacitors
nor in fans.
01
CAP
warning
There is a warning in the
capacitor.
10
FAN
warning
There is a warning in the
fan.
YES
Pr.90
Warning
information
-
-
Warning information.
-
Pr.91
Fifth fault
nOn
-
It stores information on the types of faults,
the frequency, the current and the
acceleration/deceleration condition at the
time of fault. The latest fault is automatically
stored in the ‘Pr.95
➔
First fault’.
-
Pr.92
Fourth fault
nOn
-
-
Pr.93
Third fault
nOn
-
-
Pr.94
Second fault
nOn
-
-
Pr.95
First fault
nOn
-
-
Pr.96
Reset fault
history
0
0-1
It allows clearing the fault history stored
from ‘Pr.91’ to ‘Pr.95’.
YES