SD300
POWER ELECTRONICS
238
MODBUS COMMUNICATION
Programming Parameters
Screen
Description
Modbus
Decimal
Address
Hexadecimal
Range
Modbus Range
0.00
Local speed
44353
0h1101
dr.19 to dr.20
dr.19 to dr.20
dr.2
Local torque
44354
0h1102
-180.0 to 180.0%
-1800 to 1800
ACC
Acceleration Ramp
44355
0h1103
0.0 to 600.0s
0 to 6000
dEC
Deceleration Ramp
44356
0h1104
0.0 to 600.0s
0 to 6000
drv
Control mode 1
44358
0h1106
LOCAL
REMOTE
REMOTE2
MODBUS
COMMS
PLC
0
1
3
4
5
6
Frq
Speed reference 1
44359
0h1107
LOCAL
V1
V2
I2
MDBUS
COMMS
PLC
PULSE
0
2
4
5
6
8
9
12
dr.8
Torque reference 1
44360
0h1108
LOCAL
V1
V2
I2
MDBUS
COMMS
PLC
PULSE
0
2
4
5
6
8
9
12
dr.9
Control type
44361
0h1109
V/Hz
SlipCom
S-less1
PM Sensor-less
0
2
4
6
dr.10
Torque control
44362
0h110A
N / Y
0 / 1
dr.11
Inch Frequency
44363
0h110B
dr.19 to dr.20
dr.19 to dr.20
dr.12
INCH acceleration
time
44364
0h110C
0.0 to 600.0s
0 to 6000
dr.13
INCH deceleration
time
44365
0h110D
0.0 to 600.0s
0 to 6000
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......