POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
169
Screen Description Default
value
Range
Function
Set
on
RUN
In.71
Digital input 7
Mult Vel-
A
Note:
Comes from the previous page.
OPT. DESCR. FUNCTION
54
TI
In IP66 equipment, pulse
input TI and Multi-function
terminal P5 share the
same terminal. In this
case, set parameter In.69
to 54(TI).
NO
In.85
Digital input
activation
delay
10ms
0 to
10000m
s
Set the delay time when activating the digital
input. In case any variation occurs within a
smaller time gap, the input will remain
disabled.
YES
In.86
Digital input
deactivation
delay
3ms
0 to
10000m
s
Set the delay time when disabling a digital
input. In case any variations occur within a
smaller time gap, the input will remain
enabled.
YES
In.87
Digital input
contact type
00000
0000000
to
1111111
Adjust each to 0 or 1 according to the following
table:
BIT DESCR.
0
Contact normally open (YES)
1
Contact normally closed (NC)
The assignment order is
P1, P2, …, P7
starting from the bit placed farthest to the right.
The number of Digital Inputs varies depending
on the equipment (IP20 drives integrate 7
Digital Inputs and IP66 drives integrate 5).
NO
In.89
DI scan time
1ms
1 to
5000ms
Set the time to wait before refreshing the
digital inputs configured as multireference.
NO
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......