SD300
POWER ELECTRONICS
154
DESCRIPTION OF PROGRAMMING PARAMETERS
Screen Description
Default
value
Range
Function
Set on
RUN
Note
: Comes from the previous page.
OPT. DESCR.
FUNCTION
0
No
General deceleration
is carried out until a low
voltage trip occurs.
1
KEB1
When the input power
is lost, it charges the
DC
link
with
regenerated energy.
When the input power
is restored, so does
normal operation from
energy
buffering
operation
to
the
frequency reference
operation. Operation
frequency acceleration
is set in Cn.83.
2
KEB2
When the input power
is lost, it charges the
DC
link
with
regenerated energy.
When the input power
is restored, it changes
from
the
energy
buffering operation to
the deceleration stop
operation.
The
operation frequency
deceleration time is set
in dr.4.
Cn.78
[22]
Initial value for
KEB operation 125.0%
110.0 to
200.0%
Sets the start and stop points of the kinetic
energy buffering operation. The set values
must be based on the low voltage trip level
as 100% and the stop level (Cn.79) must be
higher than the start level (Cn.78).
NO
Cn.79
Value to stop
KEB operation 130.0%
Cn.78 to
210.0%
NO
[22] Displayed when Cn.77 is not set to 0 (NO).
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......