POWER ELECTRONICS
SD300
COMMONLY USED CONFIGURATIONS
315
If the motor gets overshoot of the speed, increase the value of P, and for
the fine tune, increase the value of I. If the motor is not able to keep the
speed on,
because the speed is very “nervous”, decrease the value of P
and for the fine tune decrease the I.
For high dynamic applications, the current loop regulator might be
modified:
Parameter
Default value
Description
Set value
Cn.48
1200
Current controller P gain
1200
Cn.49
120
Current controller I gain
120
For high dynamic applications, the regulator values could be increased in
order to give stability to the system. For very slow dynamins the regulator
values could be decreased in order to give a better operation in the motor
(e.g. geting a constant torque in applications such as positive
displacement pumps)
Finally, if you have not been able to make the motor work properly, you
should initialize all parameters and retry the process from the beginning
again. Maybe the result of the autotuning was not very good and the drive
was not able to calculate properly the vector position.
Parameter
Default value
Description
Set value
dr.93
0 No
Initialization parameters
1 All parameters
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......