SD300
POWER ELECTRONICS
132
DESCRIPTION OF PROGRAMMING PARAMETERS
Screen Description Default
value
Range
Function
Set
on
RUN
Ad.17
Frequency
start DC brake 5.00Hz
dr.19 to
60.00
Set the frequency value at which the drive will
enable the DC brake. The DC Brake
operation will start once the frequency is
below this value and the time set in
parameter Ad.14 has elapsed.
NO
Ad.20
Acceleration
dwell
frequency
5.00Hz
dr.19 to
dr.20
During the acceleration process, the drive will
pause at this frequency, keeping it constant
during the time set in parameter Ad.21.
NO
Ad.21
Acceleration
dwell time
0.0s
0.0 to
60.0s
During the acceleration process, this
parameter allows to define during how long
the drive will operate at the constant
frequency set in parameter Ad.20.
NO
Ad.22
Deceleration
dwell
frequency
5.00Hz
dr.19 to
dr.20
During the deceleration process, the drive
will pause at this frequency value, remaining
constant during the time period established
in parameter Ad.23.
NO
Ad.23
Deceleration
dwell time
0.0s
0.0 to
60.0s
During the deceleration process, this
parameter allows to set how long will the
drive be operating at the constant frequency
set in parameter Ad.22.
NO
Ad.24
Use frequency
limit
N
NO
YES
Enable or disable the frequency limit.
OPT. DESCR. FUNCTION
0
NO
Frequency limit disabled.
1
YES
Frequency limit enabled.
NO
Ad.25
[11]
Frequency
lower limit
0.50Hz
0.00 to
Ad.26
Set the lower frequency limit if parameter Ad.
24 is set as YES.
YES
Ad.26
Frequency
higher limit
dr.20 Hz
[11]
Ad.25 to
dr.20
Set the upper frequency limit whenever
parameter Ad. 24 is set as YES.
NO
[10] These parameters will only be displayed if Ad.8 is set to 1 (DCBRAKE).
[11] These parameters will only be displayed if Ad.24 is set to 1 (YES).
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......