POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
181
Screen Description
Default
value
Range
Function
Set on
RUN
OU.57
Relay FDT
level
30.00Hz 0.00 to
dr.20
Value of the output frequency for digital
outputs FDT options.
YES
OU.58
Relay FDT
band
10.00Hz
0.00 to
dr.20
Detection frequency band for digital outputs
FDT options.
YES
OU.61
Pulse output
mode
Frequen
cy
0 to 15
Pulse output setting.
OPT. FUNCTION
OPT. FUNCTION
0
Frequency
8
TargetFq
1
O/pCurr
9
RampFreq
2
O/pVolt
10
SpeedFdb
3
DCLinkV
12
PIDRefVal
4
Torque
13
PIDFdbVal
5
O/pPower
14
PIDO/p
6
Idse
15
Constant
7
Iqse
YES
OU.62
Pulse output
gain
100.0%
-1000.0
to
1000.0%
Adjusts output value and offset. If
frequency is selected as an output, it will
operate according to the following
equation:
𝑇0 =
𝐹𝑟𝑒𝑞𝑢𝑒𝑛𝑐𝑦
𝑀𝑎𝑥𝐹𝑟𝑒𝑞
× 𝑇𝑂 𝑔𝑎𝑖𝑛 × 𝑇𝑂 𝐵𝑖𝑎𝑠
YES
OU.63
Pulse output
offset
0.0%
-100.0 to
100.0%
YES
OU.64
Pulse output
filter
5ms
0 to
10000ms
Sets filter time constant on analog output.
YES
OU.65
Pulse output
constant
setting
0.0%
0.0 to
100.0%
If analog output item is set to constant, the
analog pulse output is dependent on the
set parameter values.
YES
OU.66
Pulse output
monitor
0.0%
0.0 to
1000.0%
Monitors analog output value. Displays the
maximum output pulse (32kHz) as a
percentage (%) of the standard.
YES
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......