14-8
FP0
Item
Add-
ress
Name
Default
value
Descriptions
31
Wait time setting for
multi-frame
communication
6500 ms
(K2600)
10 ms to 81900 ms (K4 to K32760)
Used of default setting (K2600/6500
ms) is recommended.
Time
setting
34
Constant value settings
for scan time
0 ms
(K0)
2.5 ms to 160 ms (K1 to K64 ): Scans
once each specified time interval.
0 (K0):Normal scan
Do not set
X0 as
high-
speed
counter.
CH0
Do not set X0 as high-speed
counter.
2-phase input (X0, X1)
2-phase input (X0, X1),
Reset input (X2)
Incremental input (X0)
Incremental input (X0), Reset input
(X2)
Decremental input (X0)
Decremental input (X0),
Reset input (X2)
Individual input (X0, X1)
Individual input (X0, X1),
Reset input (X2)
Direction decision (X0, X1)
Direction decision (X0, X1),
Reset input (X2)
Input
setting
400
High-speed
counter
mode
settings
(X0 to X2)
Setting by
progra-
mming tool
software
Do not set
X1 as
high-
speed
counter.
CH1
Do not set X1 as high-speed
counter.
Incremental input (X1)
Incremental input (X1), Reset input
(X2)
Decremental input (X1)
Decremental input (X1), Reset input
(X2)
Note1) If the operation mode is set to 2-phase, individual, or direction differentiation, the setting for CH1
is invalid.
Note2) If reset input settings overlap, the setting of CH1 takes precedence.
Note3) If system register 400 to 403 have been set simultaneously for the same input relay, the following
precedence order is effective: [High-speed counter] ‘[Pulse catch]’ [Interrupt input].
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...