14-15
14.1.2 Table of Special Internal Relays for FP0
The special internal relays turn on and off under special conditions. The on and off states are not output
externally. Writing is not possible with a programming tool or an instruction.
Address
Name
Description
R9000
Self-diagnostic error
flag
Turns on when a self-diagnostic error occurs.
The self-diagnostic error code is stored in DT9000.
R9001 to
R9003
Not used
-
R9004
I/O verification error
flag
Turns on when an I/O verification error occurs.
The position number of the I/O where the verification error
was occurred is stored in DT9010.
R9005,
R9006
Not used
-
R9007
Operation error flag
(hold)
Turns on and keeps the on state shen an operation error
occurs.
The address where the error occurred is stored in DT9017.
(Indicates the first operation error which occurred).
R9008
Operation error flag
(non-hold)
Turns on for an instant when an operation error occurs.
The address where the operation error occurred is stored in
DT9018. The contents change each time a new error occurs.
R9009 Carry
flag
Turns on for an instant,
- when an overflow or underflow occurs.
– when “1” is set by one of the shift instructions.
R900A >
Flag
Turns on for an instant when the compared results become
larger in the “F60 (CMP) to F63 (DWIN) comparison
instructions.”
R900B =
Flag
Turns on for an instant,
-
when the compared results are equal in the comparison
instructions (F60 to F63).
-
when the calculated results become 0 in the arithmetic
instructions.
R900C <
Flag
Turns on for an instant when the compared results become
smaller in the “F60 (CMP) to F63 (DWIN) comparison
instructions.
R900D
Auxiliary timer
contact
Turns on when the set time elapses (set value reaches 0) in
the timing operation of the F137(STMR)/F183(DSTM)
auxiliary timer instruction.
It turns off when the trigger for auxiliary timer instruction
turns off.
R900E
Tool port error flag
This turns on when an error occurs during communication
with a programming tool.
R900F
Constant scan error
flag
Turns on when the scan time exceeds the time specified in
system register 34 during constant scan execution.
R9010
Always on relay
Always on.
R9011
Always off relay
Always off.
R9012
Scan pulse relay
Turns on and off alternately at each scan.
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...