14-130
Error
code
Name
Opera-
tion
status
Description and steps to take
FP0
FP-e
FP
Σ
FP-X
FP1/FP-M
FP2
FP2SH
FP10SH
FP3
E43
System
watching
dog timer
error
Selec-
table
Scan time required for program
execution exceeds the setting of the
system watching dog timer.
⇒
Check the program and modify it so
that the program can execute a scan
within the specified time.
Selection of operation status using
system register24:
-to continue operation,set 1
-to stop operation,set 0
A A
E44
Slave
staiton
connecting
time error
for
MEWNET-F
system
Selec-
table
The time required for slave station
connection exceeds the setting of the
system register 35.
Selection of operation status using
system register25:
-to continue operation,set 1
-to stop operation,set 0
A
A
A
A
E45
Operation
error
Selec-
table
Operation became impossible when a
high-level instruction was executed.
Selection of operation status using
system register26:
-to continue operation,set K1
-to stop operation,set K0
In the FP2,FP2SH,and FP10SH,Check
the contents of special data registers
DT90017,DT90018 to find the instruction
address where the operation error
occurred. Then correct the program.
In the FP3,Check the contents of special
data registers DT9017,and DT9018 to
find the instruction address where the
operation error occurred.Then correct
the program.
Verification is possible in FPWIN GR/Pro
at”I/O error” in the status display
function.
A A A A A A A A A
A:Available
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...