4.3
Wiring the Power Supply
S
−
LINK terminal block: MC1.5/6
−
ST
−
3.5 (Made by Phoenix Contact Co.)
Terminal name
Color of connecting cable
Description
24V
Brown
Main wire (for S
−
LINK I/O devices)
0V
Blue
D
White
G
Black
IN
−
24V
—
External power supply input for S
−
LINK
IN
−
0V
—
Suitable wires (twisted wire)
Size
AWG#20 to 16
Normal cross
−
section surface area
0.5 to 1.25mm
2
Notes
The S
−
LINK section is protected by a fuse, but if too many
input/output devices are connected, or if the current
consumption is heavy enough to cause the fuse to blow, we
recommend providing a local power supply.
A short
−
circuit between D
−
G, or between D
−
24V, triggers the
protective circuit, but there is no protection against
short
−
circuiting between G
−
24V or 0V
−
24V. Be aware that a
short
−
circuit can cause a breakdown or malfunction.
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...