Optional Memory
FP0
2
−
14
2.2
Specifications
2.2.3
Input Specifications
Item
Description
Insulation method
optical coupler
Rated input voltage
24 V DC
Rated input current
approx. 4.3 mA (at 24 V DC)
Input impedance
approx. 5.6 k
Ω
Operating voltage range
21.6 to 26.4 V DC
Input points per
common (
*
Note 1)
C10RM,
C10CRM,
C10RS,
C10CRS
6 points/common
C14RM,
C14CRM,
C14RS,
C14CRS
8 points/common
C16T, C16CT,
C16P, C16CP
8 points/common
C32T, C32CT,
C32P, C32CP
T32CT,
T32CP
16 points/common
ON voltage/ON current
19.2 V or less/3 mA or less
OFF voltage/OFF current
2.4 V or more/1 mA or more
Response time
(at 24 V DC and 25
°
C/66
°
F)
OFF
↔
ON
50
µ
s or less (at X0, X1) (
*
Note 2)
100
µ
s or less (at X2 to X5) (
*
Note 2)
2 ms or less (at X6 to XF)
ON
↔
OFF
the same as above
Operating mode indicator
LED
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) X0 through X5 are inputs for the high-speed counter and have
a fast response time. If used as normal inputs, we recommend
inserting a timer in the ladder program as chattering and noise
may be interpreted as an input signal.
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...