14-132
Error
code
Name
Opera-
tion
status
Description and steps to take
FP0
FP-e
FP
Σ
FP-X
FP1/FP-M
FP2
FP2SH
FP10SH
FP3
E50
Backup
battery
errror
Conti-
nues
The voltage of the backup battery
lowered or the backup battery of conrol
unit is not installed.
⇒
Check the installation of the backup
battery and then replace battery if
necessary.
By setting the system register 4, you can
disregard this self-diagnostic error.
A A A
A
Note
)
A A A A
E51
MEWNET-F
terminal
station
error
Conti-
nues
Terminal station setting was not properly
performed.
Check stations at both ends of the
communication path,and set them in the
terminal station using the dip switches.
A
A
A
A
E52
MEWNET-F
I/O update
synchro-
nous error
Conti-
nues
Set the INITIALIZE/TEST
selecto1inmjvbgycfrde892 r to the
INITIALIZE position while keeping the
mode selector in the RUN position.If the
same error occurs after this,please
contact your dealer.
A
A
A
A
E53
Multi-CPU
I/O regis-
tration
error
(CPU2
only)
Conti-
nues
Abnormality was detected when the multi-
CPU system ws used.
Please contact your dealer.
A
A
E54
IC memory
card back-
up battery
error
Conti-
nues
The voltage of the backup battery for the
IC memory card lowered. The BATT.LED
does not turn on.
Charge or replace the backup battry of IC
memory card.(The contents of the IC
memory card cannot be guaranteed.)
A
A
E55
IC memory
card back-
up battery
error
Cont-
inues
The voltage of the backup battery for IC
memory card lowers.The BATT.LED does
not turn on.
Charge or replace the backup battery of
IC memory card.
(The contents of the IC memory card
cannot be guaranteed.)
A
A
E56
Incompat-
ible IC
memory
card error
Cont-
inues
The IC memory card installed is not
compatible.
Replace the IC memory card compatible
with FP2SH/FP10SH.
A
A
E57
No unit for
the
configu-
ration
Conti-
nues
MEWNET-W2
The MEWNET-W2 link unit is not
installed in the slot specified using the
configuration data.
Either install a unit in the specified slot or
change the parameter.
A
A
A:Available
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...