High
−
speed Counter/Pulse Output/ PWM Output
FP0
9
−
17
9.3 High
−
speed Counter Function
Positioning operations with a double speed inverter
When X5 is turned on, Y0 and Y1 turn on and the conveyor begins moving. When the
elapsed value (DT9044 and DT9045) reaches K4500, Y1 turns off and the conveyor
begins decelerating. When the elapsed value reaches K5000, Y0 turns off and the
conveyor stops.
R101
DF
X5
R100
R100
R903A
R103
DF
R100
R101
DF/
R903A
R103
R103
R100
T0
TMX 0, K 5
R101
Y0
S
Y1
S
F61 DCMP, K 4500, DT 9044
R100
DF
R102
Y1
R
R100
R102
R900C
F1 DMV, K 0, DT 9044
F167 HC1R, K 0, K 5000, Y 0
High
−
speed signal to inverter
Reaches deceleration point
Deceleration
Completion pulse (0.5 seconds)
Positioning operations running
Positioning operations start
Start signal to inverter
Summary of Contents for FP0 Series
Page 14: ...Table of Contents FP0 xii ...
Page 16: ...Overview FP0 1 2 ...
Page 82: ...S LINK Control Unit FP0 4 2 ...
Page 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Page 96: ...I O Allocation FP0 5 2 ...
Page 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Page 102: ...Installation FP0 6 2 ...
Page 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Page 114: ...Wiring FP0 7 2 ...
Page 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Page 200: ...General use Serial Communications FP0 10 2 ...
Page 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Page 220: ...Specifications FP0 12 2 ...
Page 234: ...Dimensions FP0 13 2 ...
Page 243: ...Chapter 14 Appendix ...
Page 380: ...14 138 14 7 ASCII Codes ...